|
Bids Are invited for Custom Bid For Services - Day To Day Electrical Nature Of Works At Sasti Expn Ocm, Ballarpur Area - Making Cement Concrete Foundation Including Excavation (60 X 60 X 150) Cm Deep In1:3:6 Cement Concrete 20 X 25 Mm Stone Metal, (45 X 45 X 45) Cm /45 Cm Dia. X 45 Cmheight Plinth Duly Plastered, With Necessary Curing And Finishing Complete , Erection Of Departmentally Provided Rolled Steel Joist (Girder) Pole 100 X 116Mm(23Kg/M) With Provided Base Plate In Provided Foundation As Per Specification No. Ohpl/Rsj , Erection Of Departmentally Provided Gi Pole B Grade 80Mm Dia 6 M Long With Base Platein Provided Foundation As Per Specification Oh-Pl/Gip , Supplying & Erecting Ms Pole Bracket For Guarding/Lt Oh Line, Fabricated From Angleiron 50X50x6 Mm And 1100Mm Long For Necessary Nos. Of Provided Insulators Anderecting On Pole With 50X6mm Cl Complete As Per Specification No. Oh -Pl/Bkt , Supplying And Erecting Of Porcelain Shackle Type Medium Insulator 50 X 89 Mm Dia. With Gi (Shackle) Strips, Nuts And Bolts Complete , Making Cement Concrete Foundation Including Excavation (60X60x150) Cm Deep In 1:3:6 Cement Concrete, (20 To 25) Mm Stone Metal With Necessary Curing And Finishing Complete (For Stay) , Erection Of Acsr Conductor Of Size - 6/1-4.72 Mm (Dog) Complete. As Per Specification No. Oh- Con/Acsr , Supplying And Erecting Gi Stay Set For Poles, Including Loop Insulators At Inaccessible Height Complete With Anchor Plate 300 X 300 X 6 Mm., Straining Screw, Gi Stay Wire 7/10 Swg, Gi Stay Rod 20 Mm X 1.8 Length And Pole Cl S Duly Erected In Provided Cement Concrete Foundation , Erection Of Acsr Conductor Of Size – 6/1-3.66 Mm Complete (Mink), As Perspecification No. Oh-Con/Acsr , Supplying And Erecting Guarding Lace For H.T.O.H. Line With 8 Swg G.I. Wire To Protectthe H.T. Overhead Line With Binding Wire Of 20 Swg G.I. Wire For 75 Mm Section On Either Side , Transportationincludingloading/Unloading(Withdepartmentaltruck)Ofmsangle/Rsjoist/Pipepole/Ms Rail / Ms Channel / Tor Steel, Etc ( In 8 Hours - 1600 Kg) , Shifting Of Lighting Cable 1.1Kv 2/4/6/8 Sq.Mm In Field Shifting Of 2 Core Armored Lighting Cable Includes Loading, Unloading And Transportation To The Site By Departmental Truck, Handling, Shifting, To The Site And Arranging , (For Repairing/Shifting Of Street Light Fittings/ Flood Lights) Removal Of Fitting From The Pole/Tower And Refitting On Pole/Tower After Repair , Shifting Of Fabricated Lighting Towers Includes Disconnection, Dismantling Of Light Fittings And Control Switches From The Tower, Pit Digging Taking Out The Same, Shifting And Erecting At The Required Site, Fixing And Connection
|