Non-Liquefied Medicinal Oxygen: Characteristics: Non-Liquefied Medicinal Oxygen With A Purity Degree Of 99.5 Supplied In Steel Cylinders With A Capacity Of 2.0 To 10.0M³. Note: The Steel Cylinders Necessary For The Storage And Transport Of Medicinal Gases Will Be Provided By The Contractor On A Lending Regime (Free Loan). The Contracting Party Will Pay Exclusively For The Volume Of Gas Actually Supplied (Recharge), Measured In Cubic Meters (M³), With The Contractor Being Solely Responsible For The Maintenance, Hygiene And Validity Of The Hydrostatic Tests On The Cylinders Made Available. 6.0M³, 19.5 To 23.5 V.V. Of O2, Maximum Impurities: Thc Less Than 5Ppm, H2o Maximum 80Ppm, With Maximum 10Ppm. Note: The Steel Cylinders Necessary For The Storage And Transport Of Medical Compressed Air Will Be Provided By The Contractor On A Lease Agreement (Free Loan). The Contractor Will Pay Exclusively For The Volume Of Compressed Air Effectively Supplied (Recharge), Rental Of Medical Air Generating Plant: Rotary Screw Type Capacity 20M³. Characteristics: Rotating Screw Type, With Minimum Effective Production Capacity Of 20M³/H At Working Pressure Of 8 Bar, According To Terms Of Reference And Its Annexes, Must Be Composed Of: Two Rotating Screw Type Compressors, Working Pressure Of 125 Psi, 220V Three-Phase Voltage, Frequency 60Hz. The Medical Air System Must Follow The Technical Standards And Recommendations Of Abnt - Nb12188, Of The Ministry Of Health - Ordinance Rdc N 50 Of February 21, 2002 And Its Amendments. The System Must Meet A Minimum Effective Production Capacity Of 20 M³/H At A Working Pressure Of 8 Bar. The System Must Produce Medical Air With The Following Characteristics: N2 Balance 02 20, 4 To 21 V/V Of Oxygen Particles ≪ 0.1 Mg/M3 Waste Oil ≪ 0.1 Mg/M3 Water Vapor: 67 Ppmmax (Dew Point - 45.5 C, Referring To Atmospheric Pressure) Co2 500 Ppmmax Co 5 Ppmmax So2 1 Ppmmax Nox 2Ppm Max Odor And Taste - Free High Efficiency Coalescing Pre-Filters For Oil Removal, Reducing Level Of Moisture And Particles Up To 0.01 Microns (Remaining Oil Content Of 0.01 Mg/M3 Maximum); Bacteriological Filter Of 0.01 Micron And 99.99 Efficiency, Provided With Cartridge, Proven In Each Unit During Its Manufacturing, Allowing With Great Efficiency Retention Of Batteries: Coalescent Post-Filter And Activated Carbon With Retention Of Particles Of Up To 0.01 Microns And Oil Remains Of 0.003..., Rental Of Vacuum Generating Center: Screw Or Lobe Type, Single Stage, Minimum Flow Of 20M³/H, Operating Vacuum 690Mmhg. Features: Rental Of Vacuum Generating Plants, Of Equal Capacity, Screw Or Lobe Type, Operational Vacuum 690Mmhg, Effective At Sea Level, And Must Be Composed Of: Two Vacuum Generating Units, Air-Cooled, Minimum Suggested Flow Of 20 M³/H, Effective At Sea Level; The Medical Vacuum System Must Follow The Technical Standards And Recommendations Of Abnt Nb12.188 -. From The Ministry Of Health Ordinance Rdc 50 Of February 21, 2002. Visual And Audible Alarm System That Can Operate With The Hospitals Emergency Electrical System, In The Event Of A Breakdown Or Power Outage: The Pump Must Be Controlled By An Electrical Panel, Direct Start, Equipped With Meters, Relays, Indicated
|