Tender For Re-Electrification Of Wildlife Research Laboratory In The Department Of Zoology At Main Campus University Of Kashmir (Electrical Work) (Advertised Cost Rs. 3.20 Lac)-10 Wiring for circuit (raw power)/ submain wiring along with earth wire with the following sizes of FR PVC insulated copper conductor, single core cable in surface/ recessed in class heavy duty PVC conduit as required Note :Rates of Suitable PVC conduit included in above description for the follwing items 11 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire 12 2 x 6 sq.mm + 1 x 6 sq.mm earth wire 13 4 x 16 sq.mm + 2 x 16 sq.mm earth wire for Sub main wiring 14 Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. 25 mm 15 Group AWiring for light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed heavy duty class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. note: all items included like Conduit, wire, box, switches etc 16 Providing and fixing of inverter /UPS power pointpower point (in loop .) with 1.5 sq. mm PVC insulated copper wire , through midium classPVC Conduit pipe with all necessary accessories i/c 6Amp switches, 5 Amp 3-pin socket 2 nos. recessed in wall covered with Modular Plates i/c Modular Box & MS boxof required size i/c 1.5 sq.mm PVC Insulated copper wire of FRLS as earth wire, Point taken up to DB duly tested and commissioned note: all items included like Conduit, wire, box, switches etc. 17 Providing and fixing of Heating points using 4 sq.mmPVC insulated copper wire of FRLS through 1” 2mm heavy duty PVC conduit and providing and fixing of 6/16 Amp. of Modular Switch, socket recessed in wall covered with modular sheet/ MS box of required size including providing and fixing of 4mm² PVC insulated copper wire as earth wire, point taken up to D.B. duly tested and commissioned, complete point in all respetsnote: all items included like Conduit, wire, MS box, switches etc. 18 Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required.Upto 450 mm sweep 19 Suppyly, testing of 12”x12” flap window type exhaust fan complete with all accessories. etc . 20 Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CM/M/W) minimum 6.00, Air delivery minimum 210 Cum/Min , 350 RPM (tolerance as per IS : 374-2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required. 21 Supplying and fixing of MS fan rods upto 2 to 2.5 feet including holes with nuts,bolts, washers, end clips as required 22 Supply , fixing of 4 ft LED slim 20 watt warm110lm/w 230V Batten type lights(T5 Type) , complete in all respects. (corridor) 23 Supply , fixing of 18 Watt surface/ recess LED slim 230V, complete in all respects commertial wipro/ Havells/ Halonex/ Ladvance/ Jaquar 24 Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. 25 Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. 26 Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. 27 Supply of 5KVA Automatic Voltage Regulator (AVR) Air cooled wall mounted having input line voltage from 120 volts to 260 volts with time hi, low cut and delay protections. 28 Supply, installation, testing & commissioning of 3 kVA 1 phase Inverter with 3x200AH 12V tubuler Batteries including suitable rack, input/output leads/ Switch sockets etc. to make the system operational.Note: Item Should have minimum of two years Warrenty and free service. 29 Supply, both side termination and installation of flush mounted Enhanced Category 6 outlet. The plastic shall be high impact, flame-retardant, UL rate thermoplastic. Dust cover / blank shall be provided to protect unused faceplate openings. Termination caps and plastic cover shall be provided to protect jack wiring. D-linkSingle outlet faceplate with RJ-45 jack 30 Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the H class PVC conduit as required.( conduit included )1 run of cable 31 Dismantling of old wiring system as required Please Enable Macros to View BoQ information 32 Dismantling of old wiring system as required Please Enable Macros to View BoQ information
|