Tender For Repair/ Maintenance Of Ht Cables, Switch Gears And Relays Incl Connected Items Under Ge (W) Colaba.; 1 Material and labour of Opening the bus -bar chamber,CT chamber, PT Chamber and Meter chamberof HT 11KV, panel boardand carry out following activities as mentioned below complete all as directed and specified by Engineer-in-Charge.(Note: spare parts shall be measured & paid seperately.) :-(i) Inspecting/cleaning/overhauling of bus bar chamber by checking of bus bars, spout insulators, space heaters and removing dust with vacuum cleaner/Blower and moisture by hot air blower and checking tightness of bus bars, insulators and applying STRIPPEX(A), STRIPPEX(B)and HTtape and test with High Voltage(DC)and meggering before and after high voltage test complete.(ii) Inspecting/cleaning/overhauling of CT/PT chamberby checking of Bus bars, spout insulators, space heaters and checking of wiring system and removing dustwith vacuum cleaner/blower and moisture by hot air blower and checking tightness of bus bars, insulators and applying anti tracking paint on CTs and insulatorsand HT Tape.(iii) Inspecting/cleaning/overhauling meteringchamberby checking ofentire wiring system, all meters, selector switches, control fuses and removing dustwith vacuum cleaner/blower and moisture by hot air blower and checking tightness of wiring system. 2 Disconnecting and dismantling the existing indoor type, 11 KV horizontal draw out type VCB trolly of rupturing capacity 250/350MVA, 400/630/800 Amps from location and repair /overhaulingand carrying out with the followingactivities as mentioned below and replacement of unservicable following itmes as and where required complete all as specified and directed by Engineer-in-Charge. (Note: spare partswill be measured & paid seperately.) (i) Inspecting / overhaulingof manual / motorised spring drive mechanism by checking mechanism, motor and gear assembly, big gear assembly, stop bolt assembly, main shaft interlocking assembly, closing spring assembly, small cam with screw,motor cut -off limit switch, butter fly swich assembly and apply multi grease lubricant to function smoothly.(ii) Inspecting / overhauling oftripping assembly,earthfault release assembly, tripping coil, auxiliary switch and checking of electrical wiring system.(iii) Inspecting / overhauling /cleaning and inspecting through insulators, vacuum interuptorsby carbon cleaner solution and apply dry graphite conductive sealant for electrical contacts to avoid carbon deposits on contact surfaces.(iv) Assembling all items/components parts to the respective postion & testing the breaker with High Voltage(DC)and meggering before and after high voltage test complete. 3 Dismantling of Old Damaged/burnt spare parts from VCB and Supply and fixing in repair of following Spare partssuitable for - VCB 11 KV , 630/800 Amps indoor type of Make Schnieder(PIX -MV)/ABB(VD4) /CG/AREVA(VMX) all as specified and directed by Engineer-in-Charge. 4 Isolating Contacts flat type 5 Vaccum InterupterVG2 6 Insulating Rod 7 Closing coil 110V /24V DC 8 Tripping Coil 110V /24V DC 9 Spring Charging Motor 110V-230V AC/DC 10 Breaker Auxiliary Switch 6NO +6NC 11 Motor Cut-off switch 12 Main Drive Shaft assembly 13 Trip Fork Linkage Assembly 14 Rachet Wheel 15 Pin for Rachet 16 Handle Block Assembly 17 Closing coilassembly without coil 18 Trip coilassembly without coil 19 Motor cutt offLever assembly 20 Trip Proper support assembly 21 Release lever 22 Pin for Release lever 23 Auxiary switch drive Assembly 24 Charging Pawl 25 Buffer for Spring 26 Over Rid Stop 27 Over Rid Stop Pin 28 24 Pin Plu and Socket Assembly 29 Bus Bar Spout Insulator with CC parts for R Phase 30 Bus Bar Spout Insulator with CCparts for Y Phase 31 Bus Bar Spout Insulator with CC parts for B Phase 32 Circuit Spout Insulator with CC Parts 33 3Phase Spout Insulator assembly Bus bar /Circuit side. 34 Half Collar (Pair) 35 Raising and lowering Handle 36 TNC Switch,16Amps Recom 37 Ammeter,digital type,DM3110 Schneider 38 Voltmeter,digital type DM3210 Schneider 39 Multifunction meter digital typeEM6400NG Schneider 40 Indicating Lamps 24/110V DC LED type 41 Dismantling, overhauling and testing Potential transformer capacity 11 KV / 110 volts ACand replacement of worn out spares such as contacts, bushing, control wiring fibre plates, gaskets , transformer oil and applying multi grease to the mechenical parts & dry graphite conductive sealant to contacts etc & re-assembling the same and commissioning complete all as specified and directed by Engineer-in-Charge. (Note : Spare parts and oil will be measured and paid seperately) 42 Material and labour for painting of HT VCBcapacity 250/350MVA,11KV, 400/630/800Amps, with onecoat of synthetic enamel paint over a coat ofred oxide primerafter cleaning, scraping, and filling ofcavitiesfor out side surface and in side surfaceof VCB and writing the details such as MES No/ SM No etc on the new metallic plate of size 30x15cm and fixng the metallic plate firmy on VCBall as specified and as directed by Engineer-in-charge. 43 S&F, testing commissioning ofcurrent transformer 50-30,5+5Amps, Class1 and 5p10,15VA,18.3kA/3Sec for 11 KV horizontal draw out type VCB trolly of rupturing capacity 250/350MVA, 400/630/800 Amps, panel board complete all as directed and specified by Engineer-in-Charge. 44 T&P for Testing of primary injection by artificialloadthroughCT’s, on each multiple settingofovercurrent & earth fault relay, testing polarities, ammeter and selectorswitchandasdirected by Engineer-in-Charge. 45 T&P for Testing /Overhauling and secondary injection of over current earth fault relays/release on each multiple setting readjustment by artificial load complete all as specified including testing complete. 46 Repair/Overhauling Indoor type, 11 KV, SF 6, RMU Panel and carrying with following and all as specified and directed by engineer in Charge.Note :- (i) Including fixing ofspare parts to function RMU smoothly and rate to be included.Notes :-Spare parts and SF6 Gas will be measured and paid separatly. (i) Inspecting/overhauling of Manual/motorised spring drive mechanism by checking mechanism, Motor and gear assembly, Big gear assembly, stop bolt assembly, Main shaft interlocking assembly, closing spring assembly, Small Cam with screw, motor cut -off limit switch, Butter fly switch assembly and apply multi grease lubricant to function smoothly.(ii)Inspecting / overhauling of assembly, earth fault release assembly, tripping coil, auxiliary switch and checking of electrical wiring system.(iii)Inspecting / overhauling /cleaning and inspecting insulators, Gas Chamber by carbon cleaner solution and apply dry graphite conductive sealant for electrical contacts to avoid carbon deposits on contact surfaces.(iv) Inspecting of Gas SF6 leakage and Re filling SF6 gas as required and all as directed.(v) Overhauling/testing of Metering Panel with PT(vi) Assembling all items/components parts to the respective postion & testing the breaker with High Voltage(DC)and meggering before and after high voltage test complete.(vii) Cleaning all busbar by rubbing and by CRC liquid cleaner.(viii)Spraying two coat of anti track paint on CTs.(ix) Applying insulating boots for busbar and cables. (x) Supply and fixing all missing nut bolts for panels. 47 S&F 11 KV, SF 6,RMU Panel Spring Charging Motor, with complete mechanisim 230/110/24 Volts of existing make. 48 S&F 11 KV, SF 6,RMU Panel SF 6 Gas filling up to the indication mark complete all as specified and as directed. 49 Repair/ MaintenanceBattery Charger Circuit 240 V AC to110 V DC 20 A (with range from 10A to 20A) with inbuilt short circuit protection supply for control circuit of 11 KV VCB/RMU complete incliuding replacement of defective parts all as specified and as directed. 50 Repair/ MaintenanceDC to DC Converter 110 V DC to 24 Volt dc20 A (with range from 10A to 20A) with inbuilt short circuit protection supply for control circuit of 11 KV VCB/RMU complete incliuding replacement of defective parts all as specified and as directed 51 S&F battery SMF EP 100-12 (12V/100AH) complete all as specified and as directed 52 Dismantling old burnt Heaters and Supply Fixing Space Heater 80 Watt capacitysuitable for VCB,s /OCB in existing panel including hard ware,wiringand all as directed. 53 T&P for fault finding on HT cables of any size and any length with fault detective machine by thumbing method and suitable high voltage and all as and directed by Engineer-in-charge. 54 T&P for route tracing ofHT cables of any size and any length with fault detective machine by thumbing method and suitable high voltage and all as and directed by Engineer-in-charge. 55 Supply and fix cable jointing kit for 11 KV (earthed) grade cable for indoor termination Heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured alumunium conductor cable of size 120 sqmm to 185 sqmm all as specified. 56 Supply and fix cable jointing kit for 11 KV (earthed) grade cable for indoor termination Heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured alumunium conductor cable of size 240 sqmm to 300 sqmm all as specified. 57 Supply and fix cable jointing kit for 11 KV (earthed) grade cable for straight through Heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured alumunium conductor cable of size 120 sqmm to 185 sqmm all as specified. 58 Supply and fix cable jointing kit for 11 KV (earthed) grade cable for straight through Heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured alumunium conductor cable of size 240sqmm to 300 sqmm all as specified. 59 Supply, Installation, testing ON LOAD & commissioning of Compact motor protection relay flush mounting with display MM-10 with 110-240V AC/DC aux supply, having following protections with required mechanical cutout arrangement & required control wiring modification work to suitable new relay to existing system making good to the disturbed surface all as specified and directed.(a) Thermal over load and short circuit . (b) Earth fault and phase loss, unbalance, phase reversal.(c) Prolong starting, locked rotor and last trip data recording. 60 Supply, Installation, testing & commissioning of Under Over Voltage relay single phase system voltage 20-110 Volt AC/DC with required mechanical cutout arrangement & required control wiring modification work to suitable new relay to existing system including making to the disturbed surface all as specified and directed. 61 Material and labour for loading into truck of old OCB/VCB with the help of Crain and shifting from site to store/ substation premises and unloading complete all as specified and directed. 62 Material and labour Disconnecting, dismantling & restablising the existing indoor type, 11 KV horizontal draw out type VCB trolly of rupturing capacity 250/350MVA, 400/630/800 Amps from location and repair /overhaulingand carrying out with the followingactivities as mentioned below and replacement of unservicable following itmes as and where required complete all as specified and directed by Engineer-in-Charge. (Note: spare partswill be measured & paid seperately.) (i) Inspecting / overhaulingof manual / motorised spring drive mechanism by checking mechanism, motor and gear assembly, big gear assembly, stop bolt assembly, main shaft interlocking assembly, closing spring assembly, small cam with screw,motor cut -off limit switch, butter fly swich assembly and apply multi grease lubricant to function smoothly.(ii) Inspecting / overhauling oftripping assembly,earthfault release assembly, tripping coil, auxiliary switch and checking of electrical wiring system.(iii) Inspecting / overhauling /cleaning and inspecting through insulators, vacuum interuptorsby carbon cleaner solution and apply dry graphite conductive sealant for electrical contacts to avoid carbon deposits on contact surfaces.(iv) Assembling all items/components parts to the respective postion & testing the breaker with High Voltage(DC)and meggering before and after high voltage test complete. 63 Excavating in trenches, n exc1.5 m wide and n exc 1.5 m indepth; for foundation, etc. or for shafts, wells, cesspits,manholes, pier holes, etc. nexc 10 sq m on plan and n exc 1.5 m in depth and getting out completein soft/loose soil all as specified. 64 All as perabove item No.63.00 above but in hard/dense soil. 65 Excavationin trenches not exc. 1.5 m wide and not exc. 1.5 in depth for foundation of poles, stay assembly and laying of U/G cables etc. and getting out in soft disintegrated rocks/road cutting/RCC/PCC complete all as specified and directed. 66 Supply and providing sand/stone dust for sand cushioning for cable protection orfilling in trenches of sand in cable ducts after cleaning of ducts all as directed and specified Note:. for the purpose of payment punned thicknesswill be measured. 67 Supply and providingunreinforced pre cast cement concrete cable cover for cable protection (Ready made Covers) ofsizes Class HVPtype I with peak, flat size 300x180x40 mm putting adjecent to each other as specified. 68 Supply and laying tubes light grade, galvanized, 100 mm bore laid in trenches or under floor or fixed with poles/walls for protection of electric cable all as directed. 69 Returning,filling in soft/loose soil including spreading, levelling, watering ,well ramming in layers n.exc 25 cm complete all as specified. 70 Removing of excavated material not exc. 50m away from starting point and depositing where directed at a level not exc. 1.5m above the starting point.in soft /loose soil 71 Removing of excavated material from the site of work and transporting out of MD land complete all as specified and directed. 72 Supply,laying in trench, in duct on wall,and testing in replacement forXLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavyduty) with aluminium conductor, 11000 volts, grade cross sectional area 240 sq. mm X 3 core all as specified and as directed. 73 Supply,laying in trench, in duct on wall,and testing in replacement forXLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavyduty) with aluminium conductor, 11000 volts, grade cross sectional area 185 sq. mm X 3 core all as specified and as directed. 74 Supply,laying in trench, in duct on wall,and testing in replacement forXLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavyduty) with aluminium conductor, 11000 volts, grade cross sectional area 120 sq. mm X 3 core all as specified and as directed. 75 Manufacturing, supplying and fixing at various sub stations for SOP (Standard Operating Procedure) for VCB/ RMU Operation on farme board of size 600 mm x 900mm having fully covered by suitable plain glass as approved . Letter,symbols, MES Logo ,borders etc.on A-1 Size paper all as required colour scheme in all respects as per direction of Engineer-in-charge. 76 T&P for fault finding, confirmation and route tracing on LT cables of any size and any length with fault detective machine by thumping method and suitable high voltage and all as and directed by Engineer-in-charge. 77 Material & labour for cable jointing kit, in repair, for LT 1.1 KV grade cable for straight through joint M-Seal type for underground PVC/XLPE armoured heavy duty cable aluminum conductor of size3.5/4 core 50 Sqmmcomplete including testing & commissioning complete all as specified and directed. Make: XICON/Raychem/3M/Mahindra and Mahindra. 78 All as per aboveitem No 77.00 herein before but cable 3.5 core 70 Sq mm 79 All as per aboveitem No 77.00 herein before but cable 3.5 core 95 Sq mm 80 All as per aboveitem No 77.00 herein before but cable 3.5 core 120 Sq mm 81 All as per aboveitem No 77.00 herein before but cable 3.5 core 185 Sq mm 82 All as per aboveitem No 77.00 herein before but cable 3.5 core 240 Sq mm 83 Material & Labourfor repairs/ Overhauling/Servicing to ExistingLT electric panels by takingshut down from appropiate authority includingT&P for Attending Faults/Trippings and rectifieng /repairingthe faults in HT/LT Panels Boards/Capacitor Panels Boaeds/ MCCBs/ACBs /Change Over switches/Cable Connections/Bus Bar etc including PVC insulating Tapes/Nut boltsand all as specified and directed by Engineer-In-Charge. (i)Tightning the loose connectionsand cleaning inside/out side complete replacing all cable glands,thimbles and lugs as per the size of existing cable, applying petrolium jelly on the contactors ,providing new insulation tape to bus bars, repair to broken /hanging doors by fixing hinges or welding the door to make it servicable, spray painting as pproved colourandtesting the entire panel board after the completion of servicing up to the satisfication of Engr-in-charge complete all as specified and directed .(Note : MCCB,ACB, measured and paidseparately under relevant items of this schedule.) 84 Dismantling of Damaged/Burnt out lugs and Supply & fixing of Aluminum Lugs with PVC Insulation Tape of size 240 Sqmm to 300 Sqmm x 3.5 core complete all as specified and directed by Engr-in-charge. 85 Dismantling of Damaged/Burnt out lugs and Supply & fixing of Aluminum Lugs with PVC Insulation Tape of size 120Sqmm to 240Sqmm x 3.5 corecomplete all as specified and directed by Engr-in-charge. 86 Dismantling Air Circuit Breaker 4pole/3pole, 630Amps to 1200Amps, 415 Volts, draw out/fixed type from location and repair /overhaulingof spring drive mechanism, coil, auxiliary switch includingsetting of over loadcoil, no volt coil, tripping coil & apply multi grease for mechnical parts, cleaning and inspectingmale and female contacts and apply dry graphite conductive sealant for contacts, checking of electrical wiring system, testing, and assembling all items/components parts to the respective positionandtesting complete all as specified and directed by Engineer-in-Charge. 87 Dismantling of Old Damaged/burnt spare parts from ACB and Supply and fixing in repair of following Spare partssuitable for -ACB 415V , 630 to 1200Amps Amps indoor type of Make ; Havells/ Schneider/IndoAsian/HPL/Legrand/C&S all as specified and directed by Engineer-in-Charge. 88 Shunt Trip Device 89 Closing coil assembly 90 Mismatch Prevention Device 91 Moving contacts assembly 92 Fixed Contact assembly 93 Auxiliary Switch 94 Arc chut with hardware 95 Current Transformers 630A/5A. 96 Current Transformers 800A/5A 97 Current Transformers 1200A/5A 98 Dismantlingof old damaged Meters and Supply & fixDigital LT voltmeter with selector switch of size 96x 96mm rating 0 to 500 volt all as specified and directed. Make:AE/MECO/ Elmeasure. 99 Dismantlingof old damaged MetersSupply & fixing Digital LT Ammeter with selector switch of size 96x 96mm suitable for CT ratio 5amp, programmable type andall as specified and directed. Make:AE/MECO/ Elmeasure. 100 Dismantling of old damaged halogen fitting Supply & fixing in repairs 500 watt Incandescent/ GLS lamp halogen Lamps with holder with aluminum cover 230Volts AC for substation heating to avoid moisture completeall as specified and directed.Make:Wipro/ Surya, crompton 101 S&F of Room Heater 1000 Watt coil type in substation to avoid moisture in HT installation room complete all as specified and directed by Engr-in-charge. 102 Dismantling of old damaged Lamps and Supply & fixing in repairs 200 watt Incandescent/ GLS lamp 230Volts AC for substation heating to avoid moisture completeall as specified and directed.Make:Wipro/ Surya, crompton 103 M&L for Maint of Multi functional meter digital type 5000 LCD CI with RS485 including necessary alteration in existing panel as required for retrofit after wiring work complete all as specified & directed. 104 M&L for Maint of Multi functional meter digital type 5000 LCD CI with RS485 including necessary alteration in existing panel,SMARTCOMN EMS Energy Management System software with multiple features suitable for minimum 10 meters at existing dashboard/ computer and shall capture and provide following data for 12 months peroid:1) 30 min instantaneous data from all the meters for seven parameters- cumulative Energy, Power, Current, Voltage, Power factor and frequency. 2) Multiple combination of device and parameters for analysis and monthly and quaterly billing survey dattion a for cumulative energy and max demand.3) Specific Energy Consumption (SEC) Report and assess to features defined by user levels.4) Monitor ON, OFF, TRIP, Ready to close status of circuit breaker through E&As UNCO Module with on premise solution. 5) Provision for Breaker ON & TRIP counter, Last 20 trips date & time6) Email and SMS notification & Excel reports with charts. 105 M&L for Maint of MQTT GPRS Converter Outdoor (LoRa) Long Range Communication Accumulator suitable for communicating with multifunctional digital Meter with LoRa communication protocol and the data transfer to the software complete all as required on existing ground position as specified and directed. 106 M&L for Maintand recharge topup for 12 months peroidof 4G/5G Router all asrequired as on existing ground position including necessary data cable (low impedance ) suitable to existing ground position including necessary data cable (low impedance) suitable to transmit data of energy meter port and CAT-6 (Patch Cord) all as directed by Engr-in-Charge. 107 M & L and fabrication work with Cross arms, bracings, supports,clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint all as specifeid and diredted by Engr-in-charge. 108 M&L electrical earthing complete with GI plate Electrode of size 60 Cm X 60 Cm X 6 mm thick burried directly inground vertically at a depth not less than 2.25 mtr. below normal ground level, with top edge of earth plate at a depth not less than 1.5 mtr. below normal ground level, connected toGI earth strip 32mm x 6mmearth leadby means of bolts,nuts and washers of galvanised iron, earth lead strip protected by means of 32 mm bore dia light grade GI pipe up to switch board/panel board , all as specified and shown in MES schedule Electrical Plate No-5 of SSR Part I, including excavation and earth work in any type of soil, PCC 1:3:6 type C1 in chamber, RCC 1:2:4 type B1, 40 mm thick cover slab with 6 mm dia MS bars at 100 mm centre to centre both ways, with 6 mm dia MS hook, Charcoaldust, salt, funnel for watering complete and testing the Earth resistence and writing on the chamber by paint all as specified and as directed. Note : Value of earth resistance shall not be more than 2 Ohm. 109 M&L in repairs galvanised iron strip 32x6mm earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles in roof ofhigh rise bldg and as required by saddles not more than distatance of 50 cm between two saddles with jointing nuts, bolts /washers to wall/surface or recess of high rised buildings or burried in ground or any situation for loop all as specified and directed by the Engineer-in-Charge. 110 Supply and fixing substation insulation rubber floor mats not less than 2.5 mm thickness suitable for operation on 11 KV panels confirming to IS 15652 : 2006 all as specified and directed by Engineer-Incharge.
|