Tender For Provision Of Certain Sanctioned Work Under Ge (Af) Tech Area Gwalior.; 1 Taking down carefully all the electrical connections from the existing 200/250 KVA DG set and AMF panel, and lifting the DG with connected AMF panel and fixing the same at RDM complete all as specified and as directed.Note:1.The DG along with the AMF Panel shall be carefully lifted without causing any damage to the equipment. Any damage caused shall be repaired by the contractor at his own expense.2. The cost of necessary PCC base of appropriate size as decided by Engineer in Charge with PCC 1:2:4 type B-1 using 20mm graded stone aggregate) to accomodate DG set at the directed location shall be deemed to be included in the quoted rate.3. Testing commissioning of the DG to the extent of satisfaction of the Engr-in-charge is deemed to be included in the quoted rate. 2 Taking down carefully all the electrical connections from the existing 100 KVA DG set and AMF panel and lifting the DG with connected AMF panel and fixing the same at 24 End ORP complete all as specified and as directed.Note 1.The DG along with the AMF Panel shall be carefully lifted without causing any damage to the equipment. Any damage caused shall be repaired by the contractor at his own expense.2. . The cost of necessary PCC base of appropriate size as decided by Engineer in Charge with PCC 1:2:4 type B-1 using 20mm graded stone aggregate) to accomodate DG set at the directed location shall be deemed to be included in the quoted rate.3. Testing commissioning of the DG to the extent of satisfaction of the Engr-in-charge is deemed to be included in the quoted rate. 3 M&L bus bar box made out of 2.0 mm thick MS sheet, 3 Phase, 4 wire, 415 volts AC supply outdoor cubical type, dust and vermin proof, floor block mounting type suitable for outdoor applications of size 600mm x 600mm x 450mm, using 40mm x 40mm x5mm thick angle iron frame with shutter and locking arrangement painted with two coats of synthetic enamel paint of approved colour over a coat of red oxide primer (internally and externally) for box, height above ground 600mm and grouted 300mm below ground, legs of frame shall be grouted in PCC 1:2:4 (size 300 x 300 x 300mm block) and complete includig 04 nos 500 mm longaluminium busbar of size 40mm x 10mm ,fixed on insulators with proper colour coding including making connections with cable of size 300 sqmm with necessary lugs and chromium plated glands complete all as specified and directed. 4 Supply, Installed, Testing and Commissioning CPRI approved cubical type LTPanelfloor mounted outdoor type for 415V, 3 phase 4 wire system 50 Hz AC supply with Copper bus barduly colour coded, for neutral supported with DMC/SMC insulators colour coded with heat shrinkable sleeve having short circuit currentwith stand minimum 21 KA for one second complete connection from bus bar to breakers with suitable copper cable , factory made fabricated with CRCA sheet totally enclosed, dust weather and vermin proof for outer shell and 2 mm thick for inner shell having TPN cpper bus bar rating 1.5 times that of controlling MCCB supported on SMC insulator with short circuit withstand capacity 35 MVA for 1 second, bottom base channel MS section not less than 100mm x 50mm x 5 mm thick, entire panel shall have a common copper earth bar of size 25mm x 5mm at the rear with 2 Nos earth stud, solid connection from main bus bar to switchgears with required size of copper wiring with minimum 1.5 Sqmm PVC insulated copper conductor cable , cable alleys, cable gland plates in two half , general construction confirming to IS-8623/93 and mounted on suitable PCC foundation for the complete panel base with follwoing detailed specification & control complete with suitable fixing accessories at 310 TRU(A) Incoming:-(a) MCCB 4P,200A, 26 KA -01No (Adjustable magnetic type)(c) Indicating lamps for three phases-Qty 1 set of 3 Nos (e) Power lamp inside the panel, along with a connection from the incoming power supply. (B) Out going:-(a) MCCB 4P, 100A, 16KA -02 No(Adjustable magnetic type)(b) MCCB 4P, 63A, 16KA -02 No(Adjustable magnetic type) (c) Astronomical type street light controller with timer and contactor complete - 01 NoNote :- The rate includes the cost of earth work and PCC for grouting the panel with angle iron of size 50 x 50 x 6 mm, 90 CM below the ground level and60 CM above the ground level. 5 S&F XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 16 sq. mm 4 corecomplete all as specified and directed. 6 S&F XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 25 sq. mm 4 corecomplete all as specified and directed. 7 S&F XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 35 sq. mm 3.5 core complete all as specified and directed. 8 S&F XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 50 sq. mm 3.5 core complete all as specified and directed. 9 S&F XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 70 sq. mm 3.5 core complete all as specified and directed. 10 S&F XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 95 sq. mm 3.5 core complete all as specified and directed. 11 S&F XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 240 sq. mm 3.5 core complete all as specified and directed. 12 Excavation in trenches n exc 1.5 mtr wide and n exc 1.5 mtr depthfor foundationand laying of cable and getting out in any type soil etc complete all as specified and directed. 13 Returning, filling in, including spreading, levelling watering and well ramming in layers n.exc 25cm in soft/loose soil etc complete as specified and directed. 14 Removing of surplus excavated soil not exceeding 50 M distance and depositing where directed at a level not exceeding 1.5 m above the starting point complete all as specified and directed. 15 S&F HDPE DWC flexible pipe of Size 40 mm external & 32 mm internal dia (ISI marked) including required clamps/couplers to be fix at 1.5 mtr interval on wall to fix the pipe properly and smooth suitable for insulation & protection of GI /copper /aluminium strip of any size complete all as specified and directed. 16 S&F HDPE DWC flexible pipe of Size 50 mm external & 38 mm internal dia (ISI marked) including required clamps/couplers to be fix at 1.5 mtr interval on wall to fix the pipe properly and smooth suitable for insulation & protection of GI /copper /aluminium strip of any size complete all as specified and directed. 17 S&F HDPE DWC flexible pipe of Size 63mm external & 50 mm internal dia (ISI marked) including required clamps/couplers to be fix at 1.5 mtr interval on wall to fix the pipe properly and smooth suitable for insulation & protection of GI /copper /aluminium strip of any size complete all as specified and directed. 18 S&F HDPE DWC flexible pipe of Size 110mm external & 95 mm internal dia (ISI marked) including required clamps/couplers to be fix at 1.5 mtr interval on wall to fix the pipe properly and smooth suitable for insulation & protection of GI /copper /aluminium strip of any size complete all as specified and directed. 19 M&L for Horizontal directional drilling (HDD) Boring of holes under road, pavement, hard standing, Runway/ PTT by trenchless technology using manual technique and necessary machine including privison of HDPE pipe of sie not less than 100 mm dia suitable for 0.4 mpa working pressure complete all as specified and directed. 20 M&L for concealed sub main wiring using two single core FR-LSH PVC insulated unsheathed cable conforming to IS : 694 multi stranded copper conductor cable of size 4.0 Sqmm of voltage rating up to and including 1100 volts drawn in and including PVC concealed conduit of dia not less than 25mm with all fittings and accessories, along with one run of PVC (green colour) insulated, unsheathed, stranded copper conductor of size 4.0 Sqmm (green colour) as earth continuity conductor all as specified and directed. Note: Two runs of single-core PVC cable with one run of earth conductor and conduit shall be measured as one unit 21 Supply and fix VTPN 8 Way distribution board double door type suitable for 63 Amp MCCB complete but without MCCB complete all as specified and as directed. 22 Supply and fixing sheet metal enclosure for double door MCB DBs, phosphatised, powder coated, Single Pole & Neutral (SPN), suitable for 8 way, 240 volts,IP 43 & IK 09 fixed on wall with din rail, neutral and earth bar, in proper position all as directed by the Engineer-in-Charge. 23 Supply and fix miniature circuit breaker (MCB) of single poles and current carrying capacity 5 to 32 Amp 240V, 10 KA "B" curvein the MCB DB complete with connection testing and commissioning complete all as specified and as directed. 24 Supply and fix miniature circuit breaker (MCB) of single poles and current carrying capacity 40 Amp 240V, 10 KA "B" curvein the MCB DB complete with connection testing and commissioning complete all as specified and as directed. 25 S&F miniature circuit breaker (MCB) of TPN/FP poles and current carrying capacity 63 Amp 415V, 10 KA "B" curvein the MCB DB complete with connection testing and commissioning complete all as specified and as directed. 26 M&L for earthing complete with galvanised steel plate electrode 600x600x6mm thick buried directly in ground (top edge of the plate should not be less than 1.50Mtrs below ground level) connected to GI strip 25×4mm by means of bolts, nuts check nuts and washers of galvanised iron or steelconnected to earthing test point all as specified incl 20 mm GI tubing medium grade and necessary fitting for protection of GI strip incl laying of charcoal dust and common salt in alternate layers of 150mm th, PCC chamber using PCC(1:3:6) type C-1 using 20mm graded stone aggregate, RCC cover 40mm thick (1:2:4) type B-0 using 12.5mm graded stone aggregate reinforced with 6mm dia round bar @ 75mm C/C both ways with MS handle 8mm dia, plastering 15mm thick CM (1:6) externally up to 150mm below ground level, GI funnel with 20mm dia medium grade GI pipe for watering and wire mesh incl excavation and earth work and disposal of surplus soil complete all as specified and shown on Electrical plate No.3 of SSR Part-I (2009) and connected to earth test point incl testing and marking Bldg Nos and writing Test Results (in white) on a black painted M.S. Plate (size 300x300x3mm th) duly welded with angle iron of size 40X40x5mm, 60cm long, fixed with the earth pit chamber by grouting complete all as specified and directed.Note :- (i) GI strip 25×4mm and GI pipe medium grade, up to 7.5mtr shall be deemed to be included in the rates quoted for earthing.(ii) Excavation and earth work in any type of soil strata shall be deemed to be included in rates quoted for earthing. (iii) The rates quoted by the contractor are deemed to be included for MS sheet of size 300x300x3mm th, fixed with necessary nuts and boltson angle iron of size 40X40x5mm, 60cm long and grouted with PCC block of size 200x200x250mm(PCC 1:3:6 using 20mm grade stone aggregate including necessary earth work. 27 Supply, install commissioning and testing of split type wall mounted Air Conditioner non inverter type units indoor and outdoor of capacity 1.5 TR (4500 K Cal / hr) single phase Non CFC / HCFC suitable for 230 volts + 10% , 50 Hz, AC supply complete with cordless remote control unitat any location with minimum 3 star rating and EER 3.2 and above complete all as specified and directed.. 28 Supply, install commissioning and testing of split type wall mounted Non Inverter Air Conditioner units indoor/outdoor of capacity 2 TR (6000 K Cal / hr) single phase Non CFC / HCFC suitable for 230 volts + 10% , 50 Hz, AC supply complete with cordless remote control unitat any location with minimum 3 star rating and EER 3.2 and above complete all as specified and directed.. 29 M & L for sub main wiring with two runs of single core 4 Sq.mm for phase and neutral conductor and one run of single core 4 Sq.mm as earth wire ofmulti stranded copper conductor FR-LSH PVC insulated unsheathed cable conforming to IS : 694 drawn through in & including PVC casing & capping with fixing accessories on wall / roof surface as per relevant IS standard not less than 25 mm width and all as complete specified and directed. Note: Two runs of single-core PVC cable with one run of earth conductor and conduit shall be measured as one unit 30 Supply and Fixing industrial type socket with plug top, Single pole and neutral and earth plug 240V, 20 Amps with steel enclosure and one MCB SPN20 Amps complete all as specified and directed. 31 Supply and fixing voltage stabilizer electronic typefor automatic operation single phase naturally air cooled, indoor type, wall mounted for input variation between 150 V to 285 V with output voltage stabilized at 200V to 245 V with accuracy of + 1% and of capacity 5.0 KVA complete all as specified and directed. 32 Supply and fixing copper tubing with of special annealed pressure copper of size 3/8" bore including insulation , clip complete all as specified and directed. 33 Supply and fixing copper tubing with of special annealed pressure copper of size 5/8" bore including insulation, clip complete all as specified and directed. 34 Supply and fixing copper tubing with of special annealed pressure copperof size 1/4" bore including insulation, clip complete all as specified and directed. 35 Supply and fixing copper tubing with insulation , clip of special annealed pressure copper of size 1/2" bore complete all as specified and directed. 36 Supply and fixing PVC nylon braided industrial quality drain pipe of 20mm inner bore including fixing accessories on wall/roof etc all as directed. 37 S&F energy efficient PVC wall mounted fan300 mm sweep, white colour including fitting to existing wall, connecting to nearest electrical socket with PVC copper cable of size 3 core 1.5 sqmm in PVC felxible conduit and two pin plug top complete all as specified and directed. 38 M & L for point wiring complete with PVC insulated unsheathed, 1100 volts grade cable 1.5 Sqmm (nominal area) FRLSH type multi stranded copper conductor, single core drawn in and including not less than 20 mm dia rigid PVC conduit "medium grade" ISI marked including all conduit accessories on concealed wiringincluding concealed pressed steel terminal box of required size factory made with top cover of ISI Marked plastic laminated sheet of required colour for mounting switch, sockets, fan regulator etc including 1.5 Sqmm FRLSH type PVC insulated unsheathed cable multi-stranded copper conductor as continuous earth wire and connected to earth dolly as required at site including chases cutting& making good disturbed surface & applying finishes to match existing surface etc. all as specified for One 3 pin 5 Ampssocket point on independent board. 39 M&L for switch piano flush type single pole one way 6 amps 240 volts complete all as specified and directed. 40 M&L for socket outlet 3 pin 6 Amp flush type 240 volts complete all as specified and directed. 41 Supply and fixing sheet metal enclosure for double door MCB DBs, phosphatised, powder coated, Triple Pole & Neutral (TPN), suitable for 4 way, 415 volts,IP 43 & IK 09 with metal door fixed on wall with din rail, neutral and earth bar, in proper positioncomplete all as specified and directed. 42 Supply & fixing MCB Single Pole and Neutral (SPN) of capacity 40 to 63 Amps, 240 Volts, breaking capacity 10 KA, ‘C’ series, fixedin proper position all as directed by the Engineer-in-Charge. 43 M & L forearthing complete with galvanised steel earth plate electrode 60 cm x 60 cm x 6mm buried directly in ground vertically to depth not less than 2.25 mtr below ground level with top edge earth plate at a depth not less than 1.5 mtr below ground level, connected to earth lead of wire 4mm dia by means of nuts, bolts, check nuts & washers made of galvanised iron protection pipe light grade of 20 mm dia and watering pipe medium grade of 15 mm dia and filled alternate layer of charcoal or coke and salt , watering funnel with wire mesh, earth pit chamber and cover CI frame PCC 1:3:6 type C-2 all as shown in electrical plate No 3 of SSR Part I of 2009 connected to earthing testpoint or as directed by Engr-in-charge all specified and indicated including necessary excavationand earth work in hard / dense soil complete all as directed by EIC. 44 Supply, laying and fixing or pass through MS pipe,1100 volts sheathed PVC insulated with bare annealed copper conductor, 4 sqmm 2 core FRLSH grade at any height of building/ hangar conforming to IS : 694 complete all as specified and as directed. 45 S&F Rigid metallic steel conduit 20mm dia, including junction/terminal, all tees, bends, elbows, reducers, bell mouth tube ends, and fixing accessories such as couplers, lock nuts, saddles, pipe hooks, etc., complete all as specified and as directed. 46 M&L for concealed point wiring on wall and surface wiring on ceiling/roof with necessary arrangements with 2.5 Sqmm single core 1100 Volts grade FRLSH PVC insulated unsheathed multistranded copper conductor with and including PVC concealed conduit of medium grade with all fittings including Modular metal flush box minimum 1.6 mm thick, Modular white cover plate with frame of required module at site, for switches and sockets, including 2.5 Sqmm single core 1100 Volts grade FRLSH PVC insulated unsheathed multistranded copper conductor as earth continuity conductor connected to common earth dolly and including cutting chases in walls/floors for concealed conduit and making good disturbed surfaces area by cement mortar (1:3) and to match with the existing surface/colour by using existing oil bound distemper/white wash complete all as specified and directed for 5 Amp Switch socket combination. Note: - Cutting chase to the wall wherever required shall be included in the rate quoted for point wiring. 47 M&L for Modular socket outlet 2 in 1, 6 pins 6A and 16A, combined 2 module, complete all as specified and directed . 48 Supply, fixing, testing and commisioning Outdoor Type Oil Cooled, Isolation Transformer /415Volts of Capacity:50kVA for input voltage range 415V and output voltage range 415V, Ratio 1:1 Vector Group: Dyn 11, Delta-Star, Outdoor type with suitable IP protection With first filling of transformer oil of requisite dielectric strength up to level, efficiency more than 95%, separate neutral bushing shall be brought out for earthing potential difference between neutral to earth less than one volt with all standard, adequate number of cooling radiators, lifting hooks one set, earthing terminal two no"s complete with Overload/short circuit protection complete all as specified and directed .Note: The cost of Necessary PCC base for the isolation transformer as per the Manfacturer recommendaton is deemed to be included in the quoted rate. 49 Taking down chowkats or frames with shuttersexceeding 1.50 Sqm but not exceeding 4 Sqm each (Aluminium windows & Aluminum Doors) (without taking off shutters from the frames) including builders hardware & glass etc complete all as specified & directed. 50 S&F UPVCsound proof door frame with shutter and DGU (double glazed unit) (5T+12+5T) toughned glass (one glass transparent and one glass tinted)with cylinder of one side key, one side thumb turn and locking system including necessary builders hardware etc, junction of wall and frame sealed with sealentcomplete all as specified and as directed by Engr-in-Charge. 51 S&F UPVC luxury casement sound proof side Hung /Tilt &Turn type windows and frame with DGU (double glazed unit) (5T+12+5T) toughned glass (one glass transparent and one glass tinted)with cylinder of one side key, one side thumb turn and locking system including necessary builders hardware etc, junction of wall and frame sealed with sealentcomplete all as specified and as directed by Engr-in-Charge. 52 S&F UPVC luxury casement sound proof fixed type windows and frame with DGU (double glazed unit) (5T+12+5T) toughned glass (one glass transparent and one glass tinted)including necessary builders hardware etc, junction of wall and frame sealed with sealentcomplete all as specified and as directed by Engr-in-Charge. 53 M&L for Forming jambs,etc. to openings (to foregoing item), including cutting, toothing and properly bonding into old work, also facing, in CM 1:4 jointing and pointing to match existing work, complete. 54 M&L for Preparation of newly plastered surface andapplying two coat of distemper oil emulsion white or tinted over a coat of putty and primer complete complete all as specifiedand directed.
|