Retrofitting Of Lt Switchgear At Ss1 And Ss2 At Btps. Retrofitting Of Lt Switchgear At Ss1 And Ss2 At Btps. , Scope Of Supply: , Lt Main Distribution Board
Additional Data:
1000A, Single Front, Fixed, Compartmentalized, Floor Mounted, Al Busbar. Control Power 220Vdc. As Per Iec-61439-1&2 Standard Comprising Of Following Feeders. Incomer 1200A/1250A Acb,4P, Electrical Draw Out Type, With Protection System, Mechanical, Local And Remote Electrical Closing/Off. Qty # 3. Outgoing Feeders. 630A Acb,4P, Electrical Draw Out Type, With In Built Protection System. Qty # 3. 400A,4P, Mccb, With External Rotary Handle. Qty # 5 200A,4P, Mccb, With External Rotary Handle. Qty # 6. 100A,3Pn, Sfu Suitable For Din Type Hrc Fuse, With Rotary Handle. Qty # 4. All Acb Fitted With Ammeter, Voltmeter, Energy Meter. Indication Lamp Etc. All Mccb, Sfu With On/Off Indication Lamp. Remote Control Panel For 06 No Acb. , Lt Street Light Distribution Board
Additional Data:
As Per Iec-61439-1&2 Standard. 400A, Single Front, Fixed, Compartmentalized, Floor Mounted, Al Busbar. Comprising Of Following Feeders. Incomer 315A, 3Pn, Sfu Suitable For Din Type Hrc Fuse, With Rotary Handle. Outgoing 63A, 3Pn, Sfu Suitable For Din Type Hrc Fuse, With Rotary Handle, Astro Timer, Power Contactor, Selector Switch Etc. Qty 02. 32A, 3Pn, Sfu Suitable For Din Type Hrc Fuse, With Rotary Handle, Astro Timer, Power Contactor, Selector Switch Etc. Qty 04. Detachable Gland Plate. , Switch Gear, Acb,415V,1000A Lt Switch Gear With Acb, Mccb And Sfu Gec Acb Switch Gear With Two Incomer, Bus Coupler And Out Going Feeders.
Additional Data:
As Per Iec-61439-1&2 Standard 1000A, Single Front, Fixed, Compartmentalized, Floor Mounted, Al Busbar. Control Power 220Vdc. Comprising Of Following Feeders. Incomer 1200A/1250A Acb,4P, Electrical Draw Out Type, With Protection System, Mechanical, Local And Remote Electrical Closing/Off. Qty# 3. Outgoing Feeders. 630A Acb,4P, Electrical Draw Out Type, With In Built Protection System. Qty # 2. 400A,4P, Mccb, With External Rotary Handle. Qty # 5 200A,4P, Mccb, With External Rotary Handle. Qty # 4. Remote Control Panel For 05 No Acb. All Acb Fitted With Ammeter, Voltmeter, Energy Meter. Indication Lamp Etc. All Mccb, Sfu With On/Off Indication Lamp. , Lt Sub Distribution Board
Additional Data:
As Per Iec-61439-1&2 Standard. 800A, Single Front, Fixed, Compartmentalized, Floor Mounted, Al Busbar. Control Power 220Vdc. Comprising Of Following Feeders. Incomer 630A Acb,4P, Electrical Draw Out Type, With Protection System, Mechanical, Local And Remote Electrical Closing/Off. Qty # 1. Outgoing Feeders. 630A Acb,4P, Electrical Draw Out Type, With In Built Protection System. Qty # 2. 400A,4P, Mccb, With External Rotary Handle. Qty # 6 100A,4P, Mccb, With External Rotary Handle. Qty # 2. All Acb Fitted With Ammeter, Voltmeter, Energy Meter. Indication Lamp Etc. All Mccb, Sfu With On/Off Indication Lamp. , Scope Of Work : , Installation & Commissioning Work.
Installation & Commissioning Of Lt Panels After Dismantling Of Old Gec Make Panels. , Gst, If Any
|